CVE-2023-30757 Vulnerability Details

  /     /     /  

CVE-2023-30757 Metadata Quick Info

CVE Published: 13/06/2023 | CVE Updated: 02/08/2024 | CVE Year: 2023
Source: siemens | Vendor: Siemens | Product: Totally Integrated Automation Portal (TIA Portal) V14
Status : PUBLISHED

CVE-2023-30757 Description

A vulnerability has been identified in Totally Integrated Automation Portal (TIA Portal) V14 (All versions), Totally Integrated Automation Portal (TIA Portal) V15 (All versions), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions), Totally Integrated Automation Portal (TIA Portal) V18 (All versions), Totally Integrated Automation Portal (TIA Portal) V19 (All versions). The know-how protection feature in affected products does not properly update the encryption of existing program blocks when a project file is updated. This could allow attackers with access to the project file to recover previous - yet unprotected - versions of the project without the knowledge of the know-how protection password.

Metrics

CVSS Version: 3.1 | Base Score: 6.2 MEDIUM
Vector: CVSS:3.1/AV:L/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N/E:P/RL:T/RC:C

l➤ Exploitability Metrics:
    Attack Vector (AV)*
    Attack Complexity (AC)*
    Privileges Required (PR)*
    User Interaction (UI)*
    Scope (S)*

l➤ Impact Metrics:
    Confidentiality Impact (C)*
    Integrity Impact (I)*
    Availability Impact (A)*

Weakness Enumeration (CWE)

CWE-ID: CWE-693
CWE Name: CWE-693: Protection Mechanism Failure
Source: Siemens

Common Attack Pattern Enumeration and Classification (CAPEC)

CAPEC-ID:
CAPEC Description:


Source: NVD (National Vulnerability Database).