CVE Published: 26/07/2023 |
CVE Updated: 24/09/2024 |
CVE Year: 2022 Source: Hitachi Energy |
Vendor: Hitachi Energy |
Product: RTU500 series Status : PUBLISHED
CVE-2022-4608 Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Metrics
CVSS Version: 3.1 |
Base Score: 7.5 HIGH Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H