CVE Published: 08/11/2022 |
CVE Updated: 03/08/2024 |
CVE Year: 2022 Source: siemens |
Vendor: Siemens |
Product: POWER METER SICAM Q100 Status : PUBLISHED
CVE-2022-43398 Description
A vulnerability has been identified in POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50), POWER METER SICAM Q100 (All versions < V2.50). Affected devices do not renew the session cookie after login/logout and also accept user defined session cookies. An attacker could overwrite the stored session cookie of a user. After the victim logged in, the attacker is given access to the user\'s account through the activated session.
Metrics
CVSS Version: 3.1 |
Base Score: 7.5 HIGH Vector: CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:H/E:P/RL:O/RC:C