CVE Published: 14/09/2022 |
CVE Updated: 25/09/2024 |
CVE Year: 2022 Source: Hitachi Energy |
Vendor: Hitachi Energy |
Product: MicroSCADA X SYS600 Status : PUBLISHED
CVE-2022-2277 Description
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600\'s ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*
Metrics
CVSS Version: 3.1 |
Base Score: 7.5 HIGH Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H