CVE-2022-2081 Vulnerability Details

  /     /     /  

CVE-2022-2081 Metadata Quick Info

CVE Published: 04/01/2024 | CVE Updated: 24/09/2024 | CVE Year: 2022
Source: Hitachi Energy | Vendor: Hitachi Energy | Product: RTU500 series CMU firmware
Status : PUBLISHED

CVE-2022-2081 Description

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is enabled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500 in a high rate, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a lack of flood control which eventually if exploited causes an internal stack overflow in the HCI Modbus TCP function.

Metrics

CVSS Version: 3.1 | Base Score: 7.5 HIGH
Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

l➤ Exploitability Metrics:
    Attack Vector (AV)* NETWORK
    Attack Complexity (AC)* LOW
    Privileges Required (PR)* NONE
    User Interaction (UI)* NONE
    Scope (S)* UNCHANGED

l➤ Impact Metrics:
    Confidentiality Impact (C)* NONE
    Integrity Impact (I)* NONE
    Availability Impact (A)* HIGH

Weakness Enumeration (CWE)

CWE-ID: CWE-787
CWE Name: CWE-787 Out-of-bounds Write
Source: Hitachi Energy

Common Attack Pattern Enumeration and Classification (CAPEC)

CAPEC-ID: CAPEC-100
CAPEC Description: CAPEC-100 Overflow Buffers


Source: NVD (National Vulnerability Database).