CVE-2021-35533 Description

Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).

Metrics

CVSS Version: 3.1 | Base Score: 7.5 HIGH
Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

l➤ Exploitability Metrics:
    Attack Vector (AV)* NETWORK
    Attack Complexity (AC)* LOW
    Privileges Required (PR)* NONE
    User Interaction (UI)* NONE
    Scope (S)* UNCHANGED

l➤ Impact Metrics:
    Confidentiality Impact (C)* NONE
    Integrity Impact (I)* NONE
    Availability Impact (A)* HIGH

Weakness Enumeration (CWE)

CWE-ID: CWE-20
CWE Name: CWE-20 Improper Input Validation