CVE-2021-27391 Vulnerability Details

  /     /     /  

CVE-2021-27391 Metadata Quick Info

CVE Published: 14/09/2021 | CVE Updated: 03/08/2024 | CVE Year: 2021
Source: siemens | Vendor: Siemens | Product: APOGEE MBC (PPC) (P2 Ethernet)
Status : PUBLISHED

CVE-2021-27391 Description

A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.

Metrics

CVSS Version: 3.1 | Base Score: n/a
Vector: n/a

l➤ Exploitability Metrics:
    Attack Vector (AV)*
    Attack Complexity (AC)*
    Privileges Required (PR)*
    User Interaction (UI)*
    Scope (S)*

l➤ Impact Metrics:
    Confidentiality Impact (C)*
    Integrity Impact (I)*
    Availability Impact (A)*

Weakness Enumeration (CWE)

CWE-ID: CWE-120
CWE Name: CWE-120: Buffer Copy without Checking Size of Input ( Classic Buffer Overflow )
Source: Siemens

Common Attack Pattern Enumeration and Classification (CAPEC)

CAPEC-ID:
CAPEC Description:


Source: NVD (National Vulnerability Database).