CVE-2013-2807 Vulnerability Details

  /     /     /  

CVE-2013-2807 Metadata Quick Info

CVE Published: 26/03/2019 | CVE Updated: 06/08/2024 | CVE Year: 2013
Source: icscert | Vendor: Rockwell Automation | Product: RSLinx Enterprise Software
Status : PUBLISHED

CVE-2013-2807 Description

Rockwell Automation RSLinx Enterprise Software (LogReceiver.exe) CPR9, CPR9-SR1, CPR9-SR2, CPR9-SR3, CPR9-SR4, CPR9-SR5, CPR9-SR5.1, and CPR9-SR6 does not handle input correctly and results in a logic error if it calculates an incorrect value for the “Total Record Size” field. By sending a datagram to the service over Port 4444/UDP with the “Record Data Size” field modified to a specifically oversized value, the service will calculate an undersized value for the “Total Record Size” that will cause an out-of-bounds read access violation that leads to a service crash. The service can be recovered with a manual reboot. The patches and details pertaining to these vulnerabilities can be found at the following Rockwell Automation Security Advisory link (login is required): https://rockwellautomation.custhelp.com/app/answers/detail/a_id/537599

Metrics

CVSS Version: 3.1 | Base Score: n/a
Vector: n/a

l➤ Exploitability Metrics:
    Attack Vector (AV)*
    Attack Complexity (AC)*
    Privileges Required (PR)*
    User Interaction (UI)*
    Scope (S)*

l➤ Impact Metrics:
    Confidentiality Impact (C)*
    Integrity Impact (I)*
    Availability Impact (A)*

Weakness Enumeration (CWE)

CWE-ID: CWE-190
CWE Name: Integer overflow CWE-190
Source: Rockwell Automation

Common Attack Pattern Enumeration and Classification (CAPEC)

CAPEC-ID:
CAPEC Description:


Source: NVD (National Vulnerability Database).